Airflow management analysis to suppress data center hot spots

Citations

WEB OF SCIENCE

28
Citations

SCOPUS

33

초록

Rapid growth in the information technology (IT) industry has created an exponential increase in data. As a result, server computers must frequently be upgraded to high performance machines. Unfortunately, high-end servers and related cooling systems consume enormous amount of energy. In most data centers, hot spots occur on server inlets, which lower server reliability and durability as well as cooling efficiency, raising energy costs for businesses and consumers. Eliminating hot spots is a common challenge for all data centers. In this study, two ventilation efficiency indices, SVE 5 and SVE 4, are introduced to pinpoint hot spots. Airflow characteristics giving rise to hot spots are then analyzed more precisely. Using a CFD simulation, the effects of adjusting the vertical angle of server exhaust air on suppressing hot spots are examined. Results indicate that a vertical angle of 60 degrees can improve temperature distribution significantly, and eventually, hot spots are eliminated. This optimal performance case is validated experimentally.

키워드

Data centerSVE 4SVE 5Server exhaust angle
제목
Airflow management analysis to suppress data center hot spots
저자
Lim, Seok-YoungChang, Hyun-Jae
DOI
10.1016/j.buildenv.2021.107843
발행일
2021-06-15
유형
Article
저널명
Building and Environment