상세 보기
초록
This study analyzed the energy consumption of a building pump system that was originally equipped with a primary- secondary zone pump system. Using the HYSYS program the energy consumption of the primary pump system was compared with the primary-secondary zone pump system. The primary-secondary zone pump system consumes less energy than the originally designed primary pump system. When the distance between the machine room and each building is assumed to be equal, the primary pump system can be more efficient than the primary-secondary zone pump system with decreasing the distance. When the distance is 120 m, the primary system consumes less total annual energy than the primary-secondary zone pump system and saves 2,773 kWh. The suggested energy evaluation program can be useful if the designer seeks a more efficient pump system.
키워드
- 제목
- 건물 특성에 따른 냉수 순환 펌핑 시스템 별 에너지 소모량 분석
- 제목 (타언어)
- Energy Consumption Evaluation in Pumping System with Different Building Characteristics
- 저자
- 신동신; 박성빈; 전태익; 마강일; 김태홍; 이성구
- 발행일
- 2016
- 저널명
- 설비공학 논문집
- 권
- 28
- 호
- 6
- 페이지
- 242 ~ 247