This study reviews the discharge coefficient for thermal buoyancy natural ventilation through experimentation. We measure the air velocity at the outlet, which is needed to derive the discharge coefficient and to compare with the theoretical value. When a temperature difference exists between the inside and outside of the building, the measured discharge coefficient differs from the theoretical value with a maximum difference of 12%. The size and position of the openings have little effect on the discharge coefficient. For practical application, the theoretical discharge coefficient can be used with little modification.
키워드
Natural ventilation(자연환기); Thermal buoyancy(온도차부력); Discharge coefficeint(보정계수); Office building(오피스 빌딩); Eco-friendly energy(친환경 에너지)
- 제목
- 온도차 자연환기 이론의 유량계수에 대한 연구
- 제목 (타언어)
- A Study of Discharge Coefficient for Thermal Buoyancy Natural Ventilation
- 저자
- 신동신; 고현준; 김세형; 선지형; 윤상민; 이진영
- 발행일
- 2015
- 저널명
- 설비공학 논문집
- 권
- 27
- 호
- 12
- 페이지
- 639 ~ 644