급·배기 일체형 디퓨저의 환기 및 온열환경 유지성능에 대한 연구

A Study on The Performance of Ventilation and Maintaining Thermal Environment for a Combined Type Diffuser

초록

Installing a ventilator for an apartment house composed of over 100 dwelling units was mandated in 2006 to improve indoor air quality. In the case of mechanical ventilators, the air change rate is kept stable, however 68% of dwellers do not operate their ventilator because of an increased electrical bill and noise. In the case of natural ventilators, the former problems are settled, but there are concerns about cold draught and an increase of heating/cooling cost. Authors are developing a heat recovery type natural ventilator which is a natural ventilator equipped with total heat recovery element, and it is expected that those problems of mechanical ventilator and natural ventilator are resolved by this. The combined type diffuser of this study is an under developed fit to the heat recovery type natural ventilator above. There are no standards to evaluate the performance for this type of diffuser. Due to this issue this study investigated the performance of the ventilation and maintained a thermal environment for the combined type diffuser by comparing it with existing diffusers. The results revealed that the performances of the combined type of diffusers showed different features from the existing ones, and was estimated to be high enough in the performances above.

키워드

Combined type diffuser of supply and exhaust(급․배기 일체형 디퓨저)Heat recovery type natural ventilator(폐열회수형 자연환기설비)Effective draft temperature(유효드래프트 온도)ADPI(공기 확산 성능지표)Age of air(공기령)
제목
급·배기 일체형 디퓨저의 환기 및 온열환경 유지성능에 대한 연구
제목 (타언어)
A Study on The Performance of Ventilation and Maintaining Thermal Environment for a Combined Type Diffuser
저자
임석영장현재
DOI
10.6110/KJACR.2016.28.6.232
발행일
2016
저널명
설비공학 논문집
28
6
페이지
232 ~ 241