데이터센터용 멀티 외기이용 냉방시스템의 지역별 에너지 절감효과에 대한 연구

A Study on the Regional Energy Conservation Effects of a Multi-stage Outdoor Air Enabled Cooling System in a Data Center

초록

A Data center houses a large number of server computers, storage and etc in racks. With the rapid increase of heat generation rates per rack in a data center, energy consumption rates for cooling have been increased year by year. In this study, energy conservation effects of a MOA (multi-stage outdoor air enabled) cooling system in a data center has been investigated when it is applied to 5 different locations, Korea. As results, Energy conservation effects of the MOA cooling system was achieved at about 20% to 30%. Humidifier operation time was 40 to 55 days when supply air temperature was maintained at 13, and humidity condition was kept within the allowed range even though humidifier was off. Furthermore, humidification was not needed when supply air temperature was maintained at 25°C. In selected 5 locations in Korea, the difference of regional climatic conditions affected no more than 5% in cooling energy consumption rates.

키워드

데이터센터이코노마이저 사이클에너지 시뮬레이션에너지절약Data centerEconomizer cyclesEnergy simulationEnergy conservation
제목
데이터센터용 멀티 외기이용 냉방시스템의 지역별 에너지 절감효과에 대한 연구
제목 (타언어)
A Study on the Regional Energy Conservation Effects of a Multi-stage Outdoor Air Enabled Cooling System in a Data Center
저자
박문기장현재
DOI
10.7836/kses.2017.37.1.071
발행일
2017
저널명
한국태양에너지학회 논문집
37
1
페이지
71 ~ 80