데이터센터의 급기온도 변화가 서버 냉각 성능에 미치는 영향에 대한 연구

A Study on the Effects of Supply Air Temperature on the Server Cooling Performance in a Data Center

초록

A datacenter is a high energy consuming facility whose cooling energy consumption rate is 10~20 times larger than general office buildings. The higher the temperature of supply air from a CRAC (computer room air- conditioner) is supplied, the more energy efficient cooling is possible because of improving the COP of a chiller and advanced range of outdoor air temperature available for the economizer cycles. However, because the temperature of cold air flowing into server computers varies depending on air mixing configurations in a computer room, the proper supply air temperature must be considered based on the investigation of air mixing and heat dissipation. By these, this study aims to understand the effects of variation of the supply air temperature on the air flow distributions, temperature distributions and rack cooling efficiencies. Computational fluid dynamics (CFD) aided in conducting the investigation. As a result, the variation of the supply air temperature does not affect the air flow distributions. However, it mainly affects the temperature distribution. From the results of CFD simulations, Rack cooling indices (RCIHI and RCILO) were evaluated and showed the ideal state set at 19℃ of the supply air temperature.

키워드

Data center(데이터센터)Supply air temperature(급기온도)Rack cooling index(RCI랙 냉각 지표)Return temperature index(RTI환기온도 지표)
제목
데이터센터의 급기온도 변화가 서버 냉각 성능에 미치는 영향에 대한 연구
제목 (타언어)
A Study on the Effects of Supply Air Temperature on the Server Cooling Performance in a Data Center
저자
장현재
DOI
10.6110/KJACR.2018.30.2.083
발행일
2018
저널명
설비공학 논문집
30
2
페이지
83 ~ 91